Nuetral 2 Sizes Smaller Than Feed Wires

How many

Bob asked:
How many "hot" wires can a single neutral support?


Our  Answer:

A shared neutral is a connection in which a plurality of circuits use the same neutral connection. This is also known as a common neutral, and the circuits and neutral together are sometimes referred to as an Edison circuit.

In a 3-phase system it is legal in some jurisdictions to share a single neutral wire between all three (3) phases.  One neutral may not have two "hot" wires from the same phase.  It is good practice to use four (4) pole Circuit breakers (as opposed to the standard three pole) where the fourth pole is the neutral phase, and is hence protected against over current on the neutral conductor.  Please remember that some jurisdiction prohibit the use of shared neutrals and/or require that the neutral conductor be substantially larger than the phase conductors.

In a three-phase circuit, a Neutral is usually shared between all three Phases. Commonly the system Neutral is derived from the Wye transformer. In the case of two phases sharing one neutral, the worst-case current draw is one side has zero load and the other has full load, or when both sides have full load. The latter case results in 1 + 1@120deg = 1@60deg, i.e. the magnitude of the current in the neutral equals that of the other two wires.

In a three-phase circuit with three balanced loads, the Neutral has zero current in it when the loads are equal, and at most one unit of current in it, where the maximum load on any one branch is one unit. It is best to think of the outgoing current on the Black (L1) phase going out and coming back on say the Red (L2) and Blue (L3) phases, rather than the Neutral Phase. It is important to remember that the three Phases are out of phase by 120 degrees. There are many dangers that can occur to electrical systems that use these Edison circuits, due to harmonic currents caused by non-linear loads, such as fluorescent & HID lighting and electronic equipment containing switching power supplies.  As a result, the practice of Edison circuits is not recommended, particularly in today's heavy computer based market place.

There are only two (2) sections in the NEC that discuss common or shared neutrals:

215.4 Feeders with Common Neutral.

(A) Feeders with Common Neutral.  Two or three sets of 3-wire feeders or two sets of 4-wire or 5-wire feeders shall be permitted to utilize a common neutral.
(B) In Metal Raceway or Enclosure.  Where installed in a metal raceway or other metal enclosure, all conductors of all feeders using a common neutral shall be enclosed within the same raceway or other enclosure as required in 300.20.

225.7 Lighting Equipment Installed Outdoors.

(A) General.  For the supply of lighting equipment installed outdoors, the branch circuits shall comply with Article 210 and 225.7(B) through (D).
(B) Common Neutral.  The ampacity of the neutral conductor shall not be less than the maximum net computed load current between the neutral and all ungrounded conductors connected to any one phase of the circuit.

While the National Electric Code (NEC) still allows the practice of common or shared neutrals to occur, several other codes (including Federal Law) regulate this unfortunate practice.  The shared or common neutral practice is highly debated among the experts, and is has been primarily left in the NEC as an accepted old-school practice.  However, there is no disagreement among the experts, including advocates of the practice, that common or shared neutrals are NOT an ideal wiring technique.  The advocates simply argue that while never ideal, sharing neutral conductors between phases can be done safely in certain circumstances.

In order to prevent an overcurrent situation, when common neutrals are used, the loads must be on different phases.  If the same phase is used, the current on the neutral wire will be equal to load-1 plus load-2, possibly doubling the current and creating an unsafe over current situation.   Remember, there is no circuit protection for the neutral wire.  When overloaded, it can only heat until it burns open.  The verification of "phase alignment" is critical in order to prevent overloads.

Many problems exist with when common or shared neutrals are used in an electrical system:

  1. Possibility of over amperage if phases are not aligned properly
  2. Cannot adjust breakers at later dates due to phase alignment issues
  3. Safety hazard for personnel when servicing the equipment as neutral wires may still be "hot" even after the proper lockout/tagout procedures have been implemented
  4. Electrical noise is increased
  5. Possibility that electrical faults occurring on a shared circuit could damage equipment on the other shared circuits
  6. GFCI circuits are nearly impossible to install

Additional regulatory information:

  1. Special tied breakers are required to ensure all breakers feeding the neutral wire are disconnected (required under 29 CFR 1910.137 & 1910.301, and DOE/ID-10600)
  2. Although technically acceptable under the NEC, it is considered "bad practice" by industrial standards
  3. Industry standards consider it especially bad practice to share neutrals for circuits intended for computer systems
  4. Best-practice recommends that shared or common neutrals be sized up one gage of wire to reduce electrical noise and help prevent overcurrent scenarios.
  5. Based on interpretation, the practice of sharing neutrals may be considered illegal under certain 29 CFR 1910 regulations
  6. Certain DOE – Operation Office Architectural Engineering Standards, dated November 1994, no longer permit the use of "Edison Circuits" in new construction
  7. The Department of Energy has released ESH Bulletin 98-2 which is entitled "EDISON CIRCUITS POSE SAFETY HAZARD" which sites ORPS Report ID-LTC-WASTEMNGT-1997-0013, INEEL Lessons Learned #97283 in its requirement for immediate corrective action in removing all Edison Circuits (shared or common neutrals) from their facilities.

In order to avoid the danger of having breakers later re-arranged onto the same leg (which would create a potential overcurrent hazard), shared neutral circuits should be connected to multi-gang breakers rather than to separate single gang breakers.

When an Edison circuit is discovered, it is recommended that electricians perform one of the following modifications:

  • Install clips on the affected circuit breakers that will open when either "hot" leg of the Edison circuit is opened.
  • Post warning signs on every electrical panel in the facility indicating that Edison circuits are installed in the associated electrical systems.
  • Train all electrical workers about the hazards of "Edison Circuits".

Your company's standard lockout/tagout procedures should be modified to include a requirement to verify zero energy on the neutral line.  Additional dangers to electricians are posed by circuits with common neutrals that are controlled by switches, such as thermostats, that may close unexpectedly.  Therefore, it is important to consider the potential presence of Edison circuits.

Electricians working on sites with Edison Circuits should be trained, warning signs posted, and should consider the possibility that every circuit may be Edison circuits, and take the necessary safety precautions.


The Engineering Experts at E&S Grounding Solutions

eppdecul1968.blogspot.com

Source: https://esgrounding.com/blog/how-many-hot-wires-can-a-single-neutral-support-assuming-they-are-the-same-gauge-wire

0 Response to "Nuetral 2 Sizes Smaller Than Feed Wires"

Post a Comment

Iklan Atas Artikel

Iklan Tengah Artikel 1

Iklan Tengah Artikel 2

Iklan Bawah Artikel